Maximum DC Conductor Resistance (IEC 60228)

This reference provides maximum DC resistance values for Class 2 stranded conductors at 20°C, together with calculated reference values at 90°C.


Conductor Data Table

Type a size (e.g. “240”) to filter the table:

Nominal Area (mm²) Verified Conductor Diameter (mm) Copper @ 20°C (Ω/km) Copper @ 90°C (Ω/km) Aluminium @ 20°C (Ω/km) Aluminium @ 90°C (Ω/km)
0.536.045.9
0.7524.531.2
1.018.123.1
1.512.115.4
2.57.419.45
44.615.88
63.083.93
101.832.333.083.95
161.151.471.912.45
250.7270.9271.201.54
350.5240.6680.8681.11
508.160.3870.4940.6410.822
709.900.2680.3420.4430.568
9511.350.1930.2460.3200.410
12012.830.1530.1950.2530.324
15013.950.1240.1580.2060.264
18516.400.09910.1260.1640.210
24017.950.07540.09610.1250.160
30020.50.06010.07660.1000.128
40023.50.04700.05990.07780.0997
50026.400.03660.04670.06050.0776
63030.80.02830.03610.04690.0601
8000.02210.02820.03670.0471
100038.40.01760.02240.02910.0373
120044.00.01510.01930.02470.0317
14000.01290.01640.02120.0272
160050.30.01130.01440.01860.0238
18000.01010.01290.01650.0212
20000.00900.01150.01490.0191
25000.00720.00920.01270.0163

Technical Notes


Terminations and Installation Risk


Disclaimer

This information is provided for general technical reference only.

All values must be independently verified against:

DC resistance values do not represent full system behaviour including AC impedance, reactance or transient effects.

No liability is accepted for any loss, damage or application arising from use of this information.

Specifications, conductor constructions and manufacturer data may change without notice.